LinkQnet 10kVA MP XRT 2U Rackmount Online UPS - Requires Batteries
Engineered for mission-critical power protection, the LinkQnet 10kVA MP XRT Online UPS delivers true double-conversion performance in a space-efficient 2U rackmount design. Built for enterprise IT environments, it provides continuous clean power to protect servers, network equipment and critical infrastructure from outages and power disturbances. Designed to integrate seamlessly into modern data centres and server rooms, this UPS supports scalable battery configurations for customised runtime requirements.
Features
- Rack and Tower Convertible LCD Design - Flexible installation with clear status monitoring
- 2U Rackmount Form Factor - High power density for efficient use of standard 19" racks
- Online Double-Conversion Topology - Full digital control for continuous clean power output
- Wide Input Voltage Range - Operates from 110~286Vac for improved utility tolerance
- Generator Compatible Operation - Stable performance when powered by generators
- ECO Mode Functionality - Energy-saving operation to improve overall efficiency
- Comprehensive Communication Interfaces - RS232, USB and EPO for monitoring and control
- Cold Start Capability - Allows UPS startup without utility power
- Intelligent Fan Speed Control - Automatically adjusts cooling for quieter operation and longer fan life
- Advanced Protection Systems - Safeguards against short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault conditions
- Battery-Ready Design - Requires external batteries for flexible runtime configuration
- Enterprise-Grade Reliability - Built for data centres and critical IT environments
Specifications
Capacity
- Rated Power: 10,000VA / 9,000W
Input
- Nominal Voltage: 208 / 220 / 230 / 240Vac
- Input Voltage Range: 110~286Vac
- Power Factor: ≥0.99
- Bypass Voltage Range: Max. Voltage 220V +25% (Optional +10%, +15%, +20%), 230V +20% (Optional +10%, +15%), 240V +15% (Optional +10%), Min. Voltage: –45% (Optional –20%, –30%)
Battery
- Battery Type: VRLA
- Charging Current: 1A (Standard) / 10A (High)
Frequency
Output
- Output Voltage: 208 / 220 / 230 / 240Vac
- Output Power Factor: ≥0.99
- Output Frequency: Line Mode: ±1% / ±2% / ±4% / ±5% / ±10% (Optional), Battery Mode: 50Hz / 60Hz
- Crest Factor: 3:1
- Output Waveform: Pure Sinewave
- Harmonic Distortion (THDv): ≤2% (Linear Load), ≤5% (Non-Linear Load)
Transfer Time
- AC Mode to Battery Mode: 0ms
- Inverter to Bypass: 0ms
Overload Capability
- Line Mode: ≤110% load for 60 minutes, ≤125% load for 10 minutes, ≤150% load for 200ms, 150% Immediate Transfer to Bypass
- Bypass Mode: 63A (Breaker)
Efficiency
- Operating Efficiency: ≥92%
Standards and Protection
- Safety Standard: IEC / EN 62040-1
- EMI: IEC / EN 62040-2
- EMS: IEC / EN 62040-2
- Ingress Protection: IP20